In situations where both temperature and humidity can be critical you can keep up to speed on the current conditions using this sensor. Combining temperature and humidity into the one sensor frees up an additional intelligent sensor port on your base unit.
Monitors temperature and humidity on a single intelligent sensor port
Own SNMP OID for data collection via a network
Setup is simple with the Gateway Junior and gateway autosense function. Once plugged into the intelligent sensor port the base unit automatically detects the sensors presence and configures it for you.
All you need to do is set your thresholds for low and high warning and critical parameters. The built in graphing function of the base unit gives you a pattern of temperature or humidity trends over time.
Zertifizierungen – RoHS und WEEE
Messgenauigkeit Celsius – max. ±2,3 bei -40 ºC, min. ±0,4 bei +25 ºC und ±1,7 bei +75 ºC
Messgenauigkeit Fahrenheit – max. ±4,1 bei -40 ºF, min. ±0,9 bei +25 ºF und ±4 bei +75 ºF
Messbereich – -40° bis +75 °C Temperatur, 0 bis 100 % relative Luftfeuchtigkeit
Messauflösung – 1 Grad für Sensorfühler- und 0,1 Grad für Sicherheitsfühlereinheiten für Temperatur. 1 % für Sensorfühler- und 0,1 % für Sicherheitsfühlereinheiten für Luftfeuchtigkeit.
Temperaturstatus OID – 1.3.6.1.4.1.3854.1.2.2.1.16.1.4.X
Sensortyp – Halbleiter, mikroprozessorgesteuert
Kommunikationskabel – RJ45-Buchse zum Temperatursensor unter Verwendung eines UTP Cat5-Kabels
Sensortyp – Halbleiter, mikroprozessorgesteuert
Stromverbrauch – Typisch 10,70 mW, 2,14 mA Sensorfühler erkennt automatisch das Vorhandensein des Temperatursensors. Typisch 7,25 mW, 1,45 mA für Luftfeuchtigkeit
Stromquelle Stromversorgung über Sensorfühler. Keine zusätzliche Stromversorgung nötig.